High Expansion Foam Generator
Description
Technical specification:
Operating
procedure |
Inlet pressure | Total water flow (GPM) | By-Pass flow
(GPM) |
Expanded foam (M???/min) | Expansion |
By-Pass valve
Closed |
7 bar | 240 litres/min | nil | 136 | 500-725 |
By-Pass valve
Fully Open |
7 bar | 265 litres/min | 100 litres/min | 150 | 800-1100 |
By-Pass valve
Fully Open |
10 bar | 315 litres/min | 115 litres/min | 200 | 800-110 |